Standard 5A Meter Base.
For those that need to monitor and record power quality and the reliability of electrical supply, this power quality meter features waveform capture and harmonics. Includes datalogging plus MODBUS RS485 and software. Optional analog & digital input, outputs, relay and Ethernet modules
The Acuvim IIW is able to time stamp the event that a voltage swell or dip had occurred. The meter can save up to 50,000 events. The feature gives the user the ability to track back and see when the voltage dip or swell occurred. Most useful for determining what types of load come on throughout the day that affect the power quality.
The Acuvim IIW is also able to capture the waveform of an AC current and AC voltage up to 8 cycles (1 cycle is one complete sin wave) before and after a swell or dip have occurred. The user may set the trigger conditions determining the swells and dips. This feature helps user's analysis of dips and swells with non-swelling and non-dipping voltage and current waveforms.
The Acuvim II series are high-end multifunction power and energy meters manufactured by Accuenergy. They are the ideal choice for the monitoring and controlling of power distribution systems.
The Acuvim II series may be used as data gathering devices for intelligent power distribution systems or plant automation systems. All monitored data is available via a digital RS485 communication port running Modbus RTU protocol. Ethernet and Profibus DP communication are also options.
With its flexible, modular I/O and communication options, the Acuvim II series is the most versatile and cost-effective metering solution on the market.
Metering
Monitoring
Alarms
Limits can be set for up to 16 indicated parameters and can be set with a specified time interval. If any input of the indicated parameters is over or under its setting limit and persists over the specified time interval, the event will be recorded with time stamps and trigger the Alarm DO output. The 16 indicated parameters can be selected from any of the 51 parameters available.
DataLogging
Acuvim IIR/IIE offers 3 assignable historical logs where the majority of the metering parameters can be recorded. The onboard memory is up to 4 MB and each log size is adjustable. A real time clock allows for any logged events to be accurately time stamped.
Time of use
User can assign up to 4 different tariffs (sharp, peak, valley and normal) to different time periods within a day according to the billing requirements. The meter will calculate and accumulate energy to different tariffs according to the meter's internal clock timing and TOU settings.
The Acuvim II Series is available in two mounting options:
The standard model is ANSI C39.1 Standard Compliant with a small size 96x96 outline.
The DIN Rail compatible units are DIN 43700 Standard Compliant. The Acuvim II series also offers an optional Remote LCD display.
As the need to better understand power and energy consumption increases, Accuenergy continues to offer a simple and effective software compliment to our metering products. Combining their meters with the Acuview software suite allows Accuenergy to offer one of the most powerful yet cost effective metering and monitoring solutions in the market.